ACR Copper Pipe Size Chart: Outside Diameter, Wall Thickness and Weight

Table of Contents

An ACR copper pipe size chart is useful only when it identifies the tube’s outside diameter, wall thickness and supply form together. The same diameter can be offered with different walls, and a metric straight-tube schedule is not an inch coil schedule with the labels converted.

The tables below separate those two product groups and add calculated bare-tube weight. They help check a material schedule or estimate copper mass. System pipe sizing and allowable operating pressure still come from the approved equipment and project requirements.

Executive Summary

  • Read ACR inch sizes as outside-diameter designations, with wall thickness specified separately.
  • Keep straight lengths, pancake coils and their dimensional series identifiable.
  • Use the listed OD and wall together when calculating weight per meter.
  • Treat calculated weight as a nominal estimate, excluding packaging and manufacturing variation.
  • Confirm the selected schedule before using a catalog entry for a project.

How to Read an ACR Copper Pipe Size Chart

Begin with the supplied product

ACR means air conditioning and refrigeration. Its product specification includes more than dimensions: material condition, internal preparation and protected delivery also matter. The ACR copper tube guide explains those broader requirements. This page concentrates on dimensional lookup and weight.

A useful line item identifies whether the material is a straight tube or a coil, then gives OD, wall and supplied length. A description such as “7/8 copper” leaves the wall and packaging form unresolved. A weight copied beside that description may therefore refer to a different item.

Preserve the original dimensional series

Inch ACR sizes identify the outside diameter. In contrast, a water-tube nominal size can differ from its actual OD. Compare actual dimensions before comparing descriptions. The general copper dimension chart covers OD, ID and nominal-size terminology in more detail.

Metric catalog sizes also need care. A listed 28 mm tube remains a 28 mm product. Converting 1-1/8 inch gives 28.575 mm, so rounding that inch size to “28 mm” would lose a real dimensional difference. It could change the fit with a connection or inspection gauge.

Read wall thickness as its own field

Wall thickness determines how much metal occupies the section and affects the bore. The catalog wall is a nominal value; actual acceptance depends on the specified tolerances and measurement method. Neither an OD label nor a satisfactory total weight establishes the minimum wall at every location.

Straight ACR Copper Tube Sizes and Weight

Selected metric straight-tube schedule

Table 1 uses the selected metric OD and wall pairings on the NEXNICE ACR straight tube specifications. The listed lengths are 5 or 5.8 m. These are catalog selection data, with the ordered combination, temper, standard and availability to be confirmed.

Table 1. Metric straight tubes, selected catalog dimensions. Weight is calculated for bare C12200 copper at nominal dimensions using a reference density of 8,940 kg/m³ near room temperature. Values exclude caps, packaging and tolerances and are not measured shipment weights.

Catalog OD mmCatalog wall mmListed length mCalculated weight kg/m
281.55 / 5.81.116
351.55 / 5.81.411
421.55 / 5.81.706
542.05 / 5.82.921
76.12.05 / 5.84.162
88.92.05 / 5.84.881
1082.55 / 5.87.408

What the straight-tube table covers

The table preserves one published metric schedule. It does not imply that these rows are the complete range of ACR tubing or that each row has the same permitted service conditions. It also does not assign a hard or soft temper from the straight shape alone.

For an inch-size project, obtain the corresponding inch schedule. An absent size should stay unresolved until the applicable specification is available. Filling a gap with the nearest metric row creates a new specification that the catalog never supplied.

The listed length is the length of one piece. Multiplying the calculated kg/m by that length estimates copper mass per piece. Add pieces using their actual ordered lengths; counting every straight tube as an identical shipping unit can conceal mixed lengths in one bundle.

Pancake Coil ACR Copper Pipe Size Chart

Inch coil dimensions remain separate

Table 2 uses the inch schedule on the ACR pancake coil specifications, which identifies its source as catalog page 11. The catalog lists soft coils in 15, 30 or 50 m lengths for these entries, subject to confirmation of the selected combination.

Table 2. NEXNICE inch pancake coil schedule. OD and wall are catalog inch values; the millimeter OD is a mathematical conversion using 25.4 mm per inch. Bare-tube kg/m is calculated from the unrounded converted dimensions and a C12200 reference density of 8,940 kg/m³ near room temperature. It excludes insulation, closures, packing and manufacturing variation. The two 3/4-inch rows are separate wall options.

Catalog OD inConverted OD mmCatalog wall inCalculated weight kg/m
1/46.35000.0300.120
5/167.93750.0320.163
3/89.52500.0320.199
1/212.70000.0320.271
5/815.87500.0350.374
3/419.05000.0350.453
3/419.05000.0420.539
7/822.22500.0450.677

A diameter can have several weights

The two 3/4-inch entries show why a diameter-only weight search can mislead. Both have the same OD, but their walls contain different amounts of copper. A quotation, stock code or quantity takeoff should retain the chosen wall rather than averaging the two listed weights.

This also explains why a weight found for a hard-drawn straight tube may not match a soft coil with the same OD. Compare the dimensional rows first. Shape and temper identify the product, while the OD and wall supply the geometry used in the mass calculation.

Missing sizes need a different verified schedule

A search for 1-1/8 ACR copper pipe does not establish its availability in this particular pancake-coil schedule. That size is outside the displayed inch table. Request its actual product entry instead of extending the preceding wall thickness to a larger diameter.

Likewise, an insulated line set, a level-wound production coil and a bare pancake coil should not share a weight simply because their copper diameters look similar. Each needs the wall, length and supplied construction of the actual item.

Calculating ACR Copper Pipe Weight

Use metal area and material density

For a round, uniform bare tube, the copper cross-sectional area is π × t × (D − t), where D is OD and t is wall thickness in millimeters. Multiplying that area by the density and a one-meter length gives:

Weight in kg/m = 0.00894 × π × t × (D − t).

The coefficient uses the stated density of 8,940 kg/m³ and converts square millimeters to square meters. Both dimensions must be in millimeters. For an inch schedule, convert the OD and wall before substitution. Retain full precision during calculation, then round the final weight.

This is a theoretical mass calculation. A different specified alloy or density basis requires its own input. The result is useful for quantity estimates and comparison; it is not a weighing certificate or a pressure calculation.

Worked estimate for a coil

For this hypothetical quantity estimate, assume a 30 m bare coil with the Table 2 catalog dimensions of 7/8-inch OD and 0.045-inch wall. The converted dimensions are 22.225 mm and 1.143 mm. Using the formula gives approximately 0.67678 kg/m, so the theoretical copper mass is 20.30 kg.

The length is an assumed order selection and the mass is calculated, not an observed coil result. A carton or pallet weight will be higher because it includes packaging. Manufacturing tolerances can also move the actual copper mass above or below the nominal estimate.

Keep net copper and shipping weight separate

If a packing list reports gross weight, subtracting an arbitrary allowance will not establish net copper weight. Obtain the actual tare basis. Cartons, pallets, end caps and protective wrapping differ between shipments, so a percentage deduction is an unreliable substitute for the packing record.

For a mixed order, calculate each OD-and-wall line separately and multiply by its supplied length and quantity. Sum those line totals only after the units agree. Keep the estimate alongside the actual net and gross weights so a difference can be investigated without treating unlike quantities as an error.

Checking a Size or Weight Discrepancy

Confirm the label before measuring

Start with the item code and its dimensional series. Then compare the order, package label and inspection record. A coil identified with a rounded metric label may still have an inch-controlled wall; preserve the controlling dimensions while resolving that description.

If the paperwork agrees but a reading differs, consider the measuring location and condition. A distorted cut end can give an unrepresentative diameter. Dimensional inspection should use the agreed method on a suitable sample, while maintaining the required cleanliness of the remaining material.

Total mass cannot prove uniform wall

Weight represents the amount of metal over a length. It does not show how that metal is distributed around every cross-section. Local wall variation or a damaged area can remain hidden in an acceptable overall mass.

Resolve an unexpected result against the relevant dimensional tolerances and inspection records. Avoid declaring a tube acceptable merely because its total weight is close to a calculation. A proper review distinguishes identification errors, unit errors, packaging mass and actual dimensional nonconformity.

Conclusion

Use the table that matches the supplied form and dimensional series. Carry OD, wall and length together through the material schedule, and label theoretical weight clearly. A size chart can then support accurate quantity checks while the approved project documents continue to govern service suitability.

Frequently Asked Questions

Is ACR copper pipe measured by OD or ID?

Inch ACR copper tube is designated by its outside diameter. The bore depends on the selected wall thickness, so an OD label alone does not specify ID. Check the actual OD and wall together when comparing a tube with fittings or a project schedule.

What is the OD of 3/4 ACR copper pipe?

A 3/4-inch ACR designation corresponds to 0.750-inch OD, or 19.05 mm. A nominal 3/4-inch water-tube description uses a different naming basis. Confirm which convention the document uses before assuming that similarly labeled products will fit the same connection.

How much does 7/8 ACR copper pipe weigh?

For the listed pancake-coil entry with 7/8-inch OD and 0.045-inch wall, the calculated bare-tube weight is about 0.677 kg/m. This uses nominal geometry and the stated copper density. Other wall schedules, actual tolerances and packaging produce different weights.

Can 28 mm tube replace 1-1/8-inch ACR tube?

Do not treat them as dimensionally identical. The exact conversion of 1-1/8 inch is 28.575 mm, which differs from 28 mm. Any substitution needs confirmation against the specified tube, connection system and project requirements; rounding the designation does not establish compatibility.

Does the chart give the correct refrigerant pipe size?

No. It identifies catalog dimensions and calculated weight for defined products. Refrigerant line selection depends on the equipment, routing and approved design conditions. Use the equipment piping instructions and project schedule to select a size, then match the appropriate product entry.

Confirm Your ACR Tube Schedule

Send the required supply form, dimensional series, OD, wall, lengths and quantities with your project specification. Request an ACR tube quotation to confirm the offered schedule and the documents needed for your order.